Duct Sizing Calculator

Calculate proper HVAC duct sizes based on airflow and velocity requirements

Airflow Requirements

Method 1: Enter CFM Directly

Cubic feet per minute

Method 2: Calculate CFM from HVAC Tonnage

Typical: 400 CFM per ton

Method 3: Calculate CFM from Room Size

Higher for sunny rooms

Duct Parameters

Recommended Duct Sizes

About Duct Sizing

CFM Calculations:

  • From HVAC Tonnage: CFM = Tons × 400
  • From Room Size: CFM = Square Feet × (1 to 2)

Duct Size Formula: Duct Area = (CFM × 144) / Velocity (FPM)

Recommended Air Velocities:

  • Supply Ducts (Main): 700-900 FPM
  • Branch Ducts: 500-700 FPM
  • Return Air Ducts: 500-700 FPM

Why Proper Sizing Matters: Undersized ducts create noise, pressure drop, and reduced efficiency. Oversized ducts waste money and space while potentially causing poor air distribution.

Quick Reference Guide

Typical HVAC System Sizes:

  • 1.5 Ton = 600 CFM (600-900 sq ft)
  • 2 Ton = 800 CFM (900-1,200 sq ft)
  • 2.5 Ton = 1,000 CFM (1,200-1,500 sq ft)
  • 3 Ton = 1,200 CFM (1,500-1,800 sq ft)
  • 4 Ton = 1,600 CFM (2,000-2,400 sq ft)
  • 5 Ton = 2,000 CFM (2,400-3,000 sq ft)